Auxiliary Equipment



Excitation Control Cabinet

1.When synchronous generator  excitation  voltage and current is gernerator  excitation voltage and current rating 110%,te excitation  system ensure continuous operation
2.The excitation system voltage ratio 1.6-2 and calculated on generator when correct sequence voltage rating of 80%.allowing strong excitation time should not less than 10s
3.The excitation system voltage response time rise not more than 0.08s,fall not more than 0.15s
4.The excitation system for power supply requirements:AC380V DC220V system .voltage deviation is rating of ±15%, frequency deviation is -3~2HZ